Generator Maintenance at 250 / 500 / 1000 Hours — Full Checklist
A genset serviced on hours can run for tens of thousands of hours. One left until it breaks usually fails at the worst possible moment.
Daily / before start
- Engine oil and coolant level
- Fuel level and leaks around the unit
- Battery voltage and terminal condition
- Nothing blocking ventilation
Every 250 hours (or 6 months)
- Change engine oil and oil filter
- Change fuel filter and water separator
- Clean the air filter
- Inspect belts, hoses and clamps
- Run on load and record parameters
Every 500 hours
- Everything from 250 hours
- Replace the air filter
- Inspect and clean the radiator
- Check alternator, AVR and panel connections
- Check valve clearance per the engine manual
Every 1000 hours / annually
- Everything from 500 hours
- Replace coolant to specification
- 100% load test with performance recorded
- Inspect exhaust system and anti-vibration mounts
- Calibrate protections and function-test ATS/AMF
Rarely used standby sets
A standby genset still needs a 30-minute on-load run at least monthly. Idle machines fail precisely because they rarely run: fuel degrades, batteries drop and seals dry out. Hospitals and data centres also need an annual staged load test for audit purposes.